10.10 Discussion of a parameterization example
10.10.1 Application Conditions
• Reading with the CLV490’s autofocus function
• Reading the packages from top
• Bar code with lines running vertically on the top side of the package, tilt across from the
scan line: ±30°
• Package height: 100 to 600 mm (3.9 to 23.6 in), package width: 200 to 550 mm
(7.9 to 21.7 in), packages not guided
• Conveyer velocity: v = 1 m/s, conveyer belt width: 600 mm (23.6 in)
• Object distance between packages: min. 300 mm (11.8 in)
• Bar code: 2/5 Interleaved, module width 0.4 mm (15.7 mil), line length 15 mm (0.6 in),
PR 2.5:1, Quality 3 or 4, 14 characters with test code (mod 10)
• Do not read under plastic sheeting, do not use very dark packages
(spectral reflection > 20 %)
• 1 bar code per package
• Reading pulse is through a SICK photoelectric switch
• Output of read results via the host interface
• Parameterization of the CLV490 based on the factory defaults
Requirements:
• Testing the application for feasability with the CLV490 before buying, with the help of
the SMART calculation sheet (service provided by SICK)
• Choice of CLV490 type: here standard density line scanner (CLV490-0010)
• No objects irrelevant for reading portruding into conveyor path
Tools:
• Measuring tape (up to 3 m (9.84 ft))
• Protractor (to set up the CLV490)
• A PC with Windows and the SICK software "CLV-Setup"
• 3-core RS-232 data cable (null modem cable), pin 2 and pin 3 crossed, e. g.
no. 2014054
• These operating instructions
10.10.2 Purpose of this discussion
• To make important clarifications
• To indicate the fitting location of the CLV490
• To point out the parameters to be set in the CLV-Setup user interface
10.10.3 Instructions for solution – step by step
¾ Determine the reading range and CLV490’s installation height over the conveyor belt
¾ Determine the CLV490’s distance measurement type
¾ Mount the CLV490
¾ Parameterize the CLV490
¾ Test an application